Residential Combustion Testing Procedures

 

To ensure safe and efficient burner operation, all residential, commercial and industrial space and process heating equipment must be properly tested for:

 

Oxygen, Carbon Monoxide and Stack Temperature

The measurement for gases and temperature should be taken at the same point.  Typically, this is done by selecting a sample location ‘upstream’ from the draft diverter/hood, barometric control or any other opening, which allows room air to enter and dilute flue gases in the stack.  In larger installations it may also be necessary to extract a number of samples from inside the flue to determine the area of greatest flue gas concentration.  Another common practice is to take the flue gas sample from the ‘Hot Spot’ or the area with the highest temperature.

Make sure that the sample point is before any draft diverter/hood or barometric damper so that the flue gasses are not diluted and the stack temperature has not been decreased by surrounding air used to balance the draft. 

The sample point should also be as close to the breach area as possible, again, to obtain an accurate stack temperature.  This may also provide a more accurate O2 reading should air be entering the flue gas stream through joints in sheet metal vent connectors.  

 

When testing atmospheric, forced air heating equipment with a clamshell or sectional heat exchanger design, test each of the exhaust ports at the top of the heat exchanger.  The probe should be inserted back into each of the exhaust ports to obtain a flue gas sample, before any dilution air is mixed in.

Draft tests should be taken from a hole drilled in the stack downstream from the draft hood.

 

 

 

 

Combustion and draft testing fan assist, furnaces/boilers should be done through a hole drilled in the vent immediately above the inducer fan.

 

 

 

 

 

Condensing furnaces/boilers can be tested through a hole drilled in the plastic vent pipe (when allowed by the manufacturer or ‘local authority of jurisdiction) or taken from the exhaust termination.

In order to obtain an accurate Steady State Efficiency reading, an auxiliary thermocouple must be inserted in the combustion air intake so that a true net stack temperature is used in the calculation.

It is important to remember that the vent system on these units operates under a positive pressure.  As a result, any holes in the vent need to be sealed.

 

 

   

 

Domestic hot water heaters with the ‘bell’ shaped draft diverter on top can be accurately tested by attaching a section of copper tubing to the probe or using a flexible probe which is then inserted directly into the top of the fire tube below the diverter.

Another common practice is to insert the probe in the hole drilled for the draft test, direct it down and push it below the level of the draft hood.

 

 

   

 

 

When testing boilers with a draft diverter mounted on the back of the equipment, flue gas samples should be taken by passing the probe from one side to the other, again upstream (toward the burner) from the opening into the draft diverter.

Draft tests should be taken from a hole drilled in the vent connector immediately above the diverter.

 

 

 

 

Boilers, which have a ‘bell’ shaped draft diverter directly on top, should be tested directly below the diverter through a hole drilled in the vent connector.

Should draft tests below the diverter measure insufficient draft levels, an additional test should be performed above the diverter to determine if the reason for insufficient draft is related to a chimney problem or a draft hood problem.

It is also a good idea to test any areas with openings that provide a path for combustion air to be introduced to the flame.  These areas provide a path where flue gases can potentially be exhausted.

With forced air systems this area is generally limited to immediately in front of the burners while many styles of boilers allow secondary combustion air to also be drawn in from all around the base of the cabinet.

 

   

 

Gas and oil fired power burners should be tested up stream from the barometric, as close to the breech area as possible.

While stack draft may be an important measurement, fuel oil and gas fired power burners require draft control over the fire to maintain a proper and controlled intake of combustion air.                                                                            

Comparing stack and overfire O2 can verify that leakage between boiler sections, access door, etc is minimal and the combustion test results are accurate.

Use caution when taking over fire O2 readings. Do not expose thermocouple or sampling assembly to excess temperatures longer than necessary.

 

 

 

Acceptable Combustion Test Results

It is very important to consult with the manufacturer or their literature to determine acceptable ranges of O2, CO, Stack Temperature, Steady State Efficiency, Smoke and Draft.  Requirements for NOx and SO2 emissions (if any exist) vary from local to local.

The following ranges are generally considered acceptable for commercial/industrial units; always check with the appliance manufacturer of specific recommendations, particularly when testing residential systems as these vary considerably from manufacturer to manufacturer.

 

Atmospheric Gas Fired Burners/Fan Assist*

Oxygen (O2)                                                                                           6% to 9%

Stack Temperature (°F)                                                                           325° to 500°

Draft in Water Column Inches (WC”)                                                    -.02 WC” to -.04 WC” in the stack

Carbon Monoxide in Parts Per Million (ppm)                                       <100ppm air free 

 

Gas Fired Power Burners*                   

Oxygen (O2)                                                                                           3% to 6%

Stack Temperature (°F)                                                                          275° to 500°

Draft in Water Column Inches (WC”)                                                   -.02 WC” Overfire or PMI*

Carbon Monoxide in Parts Per Million (ppm)                                     <100ppm air free                    

 

Oil Fired Power Burners*

Oxygen (O2)                                                                                           4% to 7%

Stack Temperature (°F)                                                                          325° to 600°

Draft in Water Column Inches (WC”)                                                   -.02 WC” Overfire or PMI*

Carbon Monoxide in Parts Per Million (ppm)                                      <100ppm air free                    

Smoke                                                                                                      Zero or PMI (Bacharach smoke number)  

  *Always check with the manufacturer of a specific piece of equipment to verify acceptable combustion test results as well as overfire and stack draft readings.

 

Back to Combustion Results        Return to the Main Page