NATE
Example Questions
100
Sample Questions
By
Norm Christopherson
NATE stands for
North American Technician Excellence, a voluntary set of examinations created to
certify that technicians meet an industry standard of technician competency.
NATE claims that the exams test for what 80% of technicians should know
80% of the time.
There is a core
exam of 50 questions plus a series of “specialty exams” covering a variety
of areas including residential and light commercial air conditioning,
residential and light commercial heat pumps, residential and light commercial
gas heat as well as several other areas of specialization. Other areas of
specialization are being added. Each of the specialty exams consist of 100
additional questions in that particular specialty. The passing score for each of
the exams is 70%. For more
specific information you may go to the NATE website for yourself.
The NATE site is located at, www.natex.org
NATE also claims
that 45% of those who took the an exam without a review course or seminar were
able to pass their exam while 72% passed if they took a review course or seminar
prior to taking the NATE exam. Therefore,
it is recommended that those considering taking one or more of the exams take a
review course or seminar first.
None of these
questions are directly from the exam. They
are sample questions much like those that may appear on the actual exam to give
you an idea of what the test is like as well as an aid to reviewing for the
exam. No answers to these questions
are provided here in an effort to encourage you to actually study for yourself.
The following
sample exam contains NATE like questions that appear on the core as well as on
the specialty exams. Like the NATE
exams, they are in no particular order. In
addition, the NATE exams also contain wiring diagrams with questions about the
diagrams. Therefore, it is to your
advantage to review & practice reading and understanding HVAC wiring
diagrams.
So,
Here Is The NATE Practice Exam
Good
Luck
- A
condensing unit should be mounted on a slab that is level to:
- Allow
any accumulated water to evenly run out of the cabinet
- Increase
airflow through the fin area
- Prevent
the unit from tipping over
- Make
certain any top discharge air blows straight up
- A
simple time activated switch is an example of a control that does not use:
- Feedback
- Electronics
- Calibration
- Manual
adjustment
- Which
of the following systems would typically require a blower with a 2000 cfm
output?
- 2-ton
ac system
- 3-ton
ac system
- 5-ton
ac system
- 7.5-ton
ac system
- A
typical induced draft furnace uses a blower-off delay in the cooling mode
to:
- Increase
the efficiency of the system
- Air
wash the coil on shutdown
- Minimize
dehumidification at the coil
- Prevent
blowing moisture off the coil on shut off
- 3,412
BTU
- 1
watt
- 3.4
watts
- 1
kilowatt
- 3.4
kilowatts
- Which
of the following would a technician use to check the operating sequence of
an air conditioning system?
- Schematic
- Pictorial
diagram
- Illustration
- Isometric
drawing
- Gas
heating systems on roofs or other elevated locations shall be accessible by
way of the building if the building is taller than;
- 10
feet
- 15
feet
- 20
feet
- 25
feet
- Rafters
in typical residential construction are how far apart?
- 12
inches
- 14
inches
- 16
inches
- 18
inches
- Which
of the following components is energized first after an intermittent
ignition gas furnace calls for heat?
- Induced
draft motor
- Pilot
valve
- Blower
motor
- Gas
valve
- To
have a system automatically switch to heating or cooling as the load
changes, the thermostat:
- System
switch should be in auto
- System
switch should be in off
- System
switch should be on
- Fan
switch should be in auto
- A
typical heat pump uses a high-pressure control to shut off the compressor if
the condensing pressure becomes excessive. The control uses a switch that
makes the compressor contact on a pressure
- Rise
at the compressor discharge
- Fall
at the compressor discharge
- Difference
between the high and low side
- Combination
of the high and low side
- Which
of the following is typically covered by local codes?
- Minimum
cfm per outlet
- Maximum
length of a trunk
- Termination
of condensate line
- Refrigerant
charge
- What
is the difference between the wiring of an electromechanical thermostat and
an electronic thermostat?
- Both
the hot leg and the common of a 120-volt supply must be run to the
electronic thermostat.
- Typically
there is no difference, they are designed to be interchangeable
- Wire
size used on the electronic thermostat must be larger
- Both
the low voltage hot and common must be run to the electronic thermostat.
- A
secondary drain pan is used when an air conditioning system is located:
- Above
a ceiling
- In
a closet
- Below
grade
- More
than 30 feet from a useable drain
- A
person is sitting near a cold window on a winter day. They are losing heat
to the cold window by:
- Conduction
- Convection
- Radiation
- Evaporation
- In
electrical wiring, the black conductor usually indicates;
- The
hot conductor
- The
neutral conductor
- The
ground wire
- The
safety wire
- Which
of the following is the correct equation for determining wattage in an
electrical circuit?
- W
= E times I
- W
= E/I
- W
= I/R
- W
= E times R
- The
rpm of a motor is determined by:
- The
motor’s voltage
- The
motor’s amperage
- The
number of poles
- The
size of the motor windings
- An
ohmmeter reading of infinity across a switch means;
- The
switch is open
- The
switch is closed
- The
switch is good
- The
switch is bad
- The
synchronous speed of a four pole 60 Hz single phase motor is:
- 3600
rpm
- 1500
rpm
- 3450
rpm
- 1800
rpm
- Contactors
are rated according to the maximum amperage through the:
- Coil
- Contacts
- Thermostat
- Fuse
- Lowering
the airflow over an evaporator will:
- Increase
the temperature drop of the air and increase the amount of moisture
removed from the air.
- Decrease
the temperature drop of the air and increase the amount of moisture
removed from the air.
- Increase
the temperature drop of the air and decrease the amount of moisture
removed from the air.
- Decrease
the temperature drop of the air and decrease the amount of moisture
removed from the air.
- What
is the temperature rise of 250 cfm of air if an electric heater adds 8,500
btuh to the air?
- 18
degrees F
- 27
degrees F
- 31.5
degrees F
- 40
degrees F
- When
a compressor service valve is located on the compressor discharge and is
back-seated;
- The
compressor is connected to the discharge piping.
- The
back-seat port is closed to the compressor.
- The
front-seat port is open to the compressor.
- All
of the above are true.
- The
maximum secondary amperage of a 40VA, 240 by 24 volt control transformer
would be;
- 1.6
amps
- 6
amps
- 10.5
amps
- .16
amps
- A
combination electrode/nozzle gauge can be used to perform which of the
following tasks?
- Remove
the spark electrode
- Remove
the burner nozzle head
- Measure
the nozzle pressure
- Position
the nozzle to the burner head
- A
single trunk duct system that extends in one or two directions from the unit
and has multiple branches is a (an)
- Perimeter
duct system
- Extended
plenum duct system
- Radial
duct system
- Reducing
trunk system
- After
cutting copper tubing, the tube edge should be cleaned with a:
- Wire
brush
- Hacksaw
blade
- Round
file
- Reamer
- Which
of the following is covered by the National Fire Protection Code?
- Wire
sizing
- Use
of return air sensors
- Locations
of service platforms
- Clearances
around condensing units.
- Maintaining
manufacturer specified clearances on all sides of a condensing unit is:
- Necessary
in residential applications only
- Necessary
in commercial applications only
- Only
necessary if required by local codes
- Necessary
whenever locating the equipment
- Of
the following, which is most likely powered by a supply voltage of 240V
single phase?
- Natural
gas furnace
- Residential
condensing unit
- Commercial
packaged unit
- Residential
humidifier
- Which
of the following would be considered a good location to mount a wall
thermostat?
- In
a kitchen
- In
a bathroom
- On
an exterior wall
- Near
a return grille
- To
have a system automatically switch to heating or cooling as the load
changes, the thermostat must have:
- System
switch set in the cooling position
- System
switch set in the heating position
- Fan
switch set in the auto position
- System
switch set in the auto position
- A
heat pump operating in the heating mode with inadequate airflow across the
indoor coil will typically have which of the following symptoms?
- A
higher than normal temperature rise across the outdoor coil
- A
low than normal temperature rise across the outdoor coil
- A
higher than normal temperature rise across the indoor coil
- A
lower than normal temperature rise across the indoor coil
- Condensate
piping must be properly trapped to prevent:
- Ice
formation in colder temperatures
- Condensate
running off the evaporator coil
- Condensate
overflowing the drain pan
- Excessive
air noise in the piping
- A
BTU is defined as the amount of heat that must be added to one ________ of
water to raise its temperature one degree Fahrenheit.
- Pound
- Ounce
- Quart
- Gallon
- In a
simple resistive circuit, the voltage is 24 volts and the current is 8 amps.
According to Ohm’s law the resistance is:
- 16
ohms
- 3
ohms
- 192
ohms
- .5
ohms
- A
traverse joint is used to connect:
- Electrical
wiring
- Ductwork
- Refrigerant
piping
- Condensate
pipe
- To
determine the amount of sensible heat added to the refrigerant above the
saturation point in an evaporator the installer would:
- Perform
a subcooling check on the liquid line
- Perform
a superheat check on the evaporator line
- Perform
a cfm check across the evaporator coil
- Perform
a delta T check across the evaporator coil
- To
check a de-energized, normally open relay for fused contacts, a VOM would be
set to check:
- Amps
- Voltage
- Current
- Ohms
- Which
of the following oil furnace components should be replaced annually?
- Burner
head
- Fuel
filter
- Flame
prover
- Combustion
chamber
- Pigtail
120 volt wires should be connected to the supply wiring by twisting the
appropriate wires together insulating and securing each connection with:
- Duct
tape
- Plastic
tape
- Wire
nuts
- Rubber
electrical tape
- Which
of the following components is typically used only on induced draft
condensing gas furnaces?
- Electronic
fan control
- Hot
surface ignition
- Induced
draft blower motor
- Secondary
heat exchanger
- Proper
control of temperature, humidity, air movement, air cleanliness and fresh
air ventilation is:
- To
achieve a total comfort level in residential HVAC applications only.
- To
achieve a total comfort level in commercial HVAC applications only.
- To
achieve a total comfort level in any structure.
- To
achieve a total comfort level in Southern states only.
- 7,000
BTU is approximately equal to _______ KW.
- One
- Two
- Three
- Four
- Which
precaution should an installer perform to keep copper from oxidizing
internally while brazing a connector to the tube?
- Hold
the torch flame centered over the connector
- Purge
the tube with an inert gas such as nitrogen
- Increase
torch flame to its maximum setting
- Hold
the torch flame on the tubing only
- After
connecting two sections of metal ductwork using drive cleats, you should:
- Bend
the ends of the drives over the duct
- Bend
the ends of the drives away from the duct
- Cut
the ends of the drives off
- Crimp
the ends of the drives and cut off
- The
term “sheathing” in the building trade refers to:
- Lumber
used between roof beams or rafters as a base for roofing material
- Lumber
used to brace interior and exterior walls
- Interior
sheet rock
- Plywood
decking in an attic
- Which
of the following areas of metal air duct design is often governed by
municipal codes?
- The
size of air ducts
- The
number of duct fittings
- Thickness
of duct insulation
- Type
of connections made at duct joints
- A
customer needs the outdoor condensing unit replaced. Which of the following
should the size of the outdoor unit be based upon?
- The
cooling load of the space
- The
capacity of the evaporator
- The
size of the slab
- The
available clearances around the unit
- Customer
complaints of “cold air blowing” from the registers of a properly
charged heat pump system may be rectified by:
- All
supply registers are slightly undersized to increase air velocity
- Any
sidewall mounted supply registers are slightly oversized to increase air
velocity
- Only
ceiling supply registers are slightly undersized to increase air velocity
- All
supply registers are sized correctly for both throw and velocity
- Fresh
air intake ducts, used to route outdoor air to interior spaces, connect to
the:
- Vent
piping
- Combustion
air duct
- Supply
side of the duct system
- Return
side of the duct system
- According
to the Uniform Mechanical Code, an attic-mounted furnace must have a
permanently mounted light fixture. Where
must the switch which controls this light be located?
- At
the main circuit panel
- Within
reach of the furnace
- Within
sight of the furnace
- At
the required passageway opening
- In
the following sentence, which of the choices below would best simplify and
still express the nearest meaning of the statement?
“In my opinion, the new thermostat design is a change for the
better”.
- An
improvement
- A
step in the right direction
- A
help
- A
badly needed modification
- Metal
duct that has hung for several years must be checked for sags and
misalignments because:
- They
can place excessive stress on joints and seals
- They
increase static pressure in the duct
- They
decrease static pressure in the duct
- They
increase CFM at the diffusers
- The
typical procedure for repairing a small tear in the outer foil covering of a
ductboard plenum is to:
- Cover
the tear with a vapor barrier such as a piece of plastic
- Cover
the tear with an approved foil tape
- Wrap
the section of ductboard with insulation
- Cut
out an area 2 inches larger than the cut and insert a replacement plug
- A
thermistor is a component used in an electronic wall thermostat to measure:
- Temperature
- Humidity
- Atmospheric
pressure
- Barometric
pressure
- Two-stage
heat, single-stage cool thermostats are typically used on dual fuel heat
pump systems that use oil heat for second stage heating.
How would the heat pump operate if the second stage of the thermostat
had an open circuit on an extremely cold day? Assume the emergency heat
switch is not turned on.
- The
heat pump will operate on calls for heat without energizing the oil
furnace.
- The
oil furnace will operate on calls for heat without energizing the heat
pump.
- Neither
the heat pump nor the oil furnace will operate in heating modes.
- The
oil furnace will operate in emergency heat mode only.
- The
slope of the condensate lines in an attic are often set by:
- Uniform
Mechanical Code
- Underwriter
- AGA
- ARI
- Which
of the following joints, when properly done, will best join a copper tube to
a copper fitting?
- Compression
- Flare
- Sweat
- Interference
- Suction
line refrigerant pressure and temperature are measurements needed to
determine the:
- Air
temperatures entering and leaving the evaporator coil.
- Amount
of refrigerant in a system.
- Subcooling
of refrigerant leaving a condensing coil.
- Superheat
in the refrigerant leaving an evaporator.
- On
startup, a natural gas heating system has “cold air” blowing from the
registers. What could be the problem?
- Burner
manifold pressure is too high.
- Supply
duct runs are too short.
- Blower
“ON” delay is set too short.
- Blower
“ON” delay is set too long.
- A
PSC condenser fan motor is not operating but the compressor runs.
A voltage check of the condenser fan motor shows no voltage at the
motor. Which of the following
may be the cause?
- Open
run capacitor
- Shorted
run capacitor
- Open
motor windings
- Poor
or open wiring connection
- Which
of the following statements is true concerning state and local codes and
regulations?
- Local
codes never override state codes.
- Local
codes always override state codes.
- State
codes always contain regulations that are more strict than local codes.
- Local
codes must be followed if they are more strict than state codes.
- Which
of the following instruments would typically be used to measure static and
total pressure in a duct system?
- Psychrometer
- Diaphragm
type differential pressure gauge
- Portable
air hood
- Anemometer
- Which
of the following instruments must be used with the power de-energized?
- Voltmeter
- Ohmmeter
- Ammeter
- Wattmeter
- A
customer asks that you do something that your company rules specifically
prohibit. When responding to their request you should:
- Tell
the customer you cannot comply with their request and leave it at that.
- Explore
with the customer the circumstances under which you might do it.
- Tell
the customer you cannot comply with their request and offer a brief
explanation why you can’t.
- Whenever
possible prevent a conflict and go ahead and do it.
- Blower
belt noise is caused by which of the following?
- Over
voltage to the motor.
- Worn
pulley
- Under
voltage to the motor.
- Wrong
blower whee
- While
checking the installation of attic mounted flexible duct, you find 7 to 9
foot spacing between duct supports. What
steps if any, should be taken?
- No
steps are necessary unless the spacing is greater than 10 feet.
- No
steps are necessary since the spacings are greater than 5 feet.
- All
supports must be relocated to maintain a maximum spacing of 5 feet.
- All
supports must be relocated to maintain a minimum spacing of 7 feet.
- A
vapor charged temperature control uses what in its power element?
- Oil
- Water
- Antifreeze
- Refrigerant
- Isolation
collars are typically added to ductwork to:
- Reduce
vibration noise
- Reduce
static pressure
- Reduce
heat gain
- Increase
air velocity
- On a
typical 120 volt three prong electrical receptacle, the hot wire should be:
- The
narrow slot
- The
wide slot
- Both
the narrow and wide slots
- The
round slot
- Each
phase of three-phase power is ______ degrees out of phase from each other.
- 60
degrees
- 45
degrees
- 90
degrees
- 120
degrees
- Two
5mfd capacitors are in series with one another. The total capacitance of the two is:
- 2.5mfd
- 5mfd
- 10mfd
- None
of these.
- Three
10mfd capacitors are connected in parallel with each other.
The total capacitance of the three is:
- 10mfd
- 20mfd
- 30mfd
- None
of these
- The
air temperature drop across an evaporator is measured and determined to be
30 degrees Fahrenheit. Which of
the following is most likely true?
- There
is too much evaporator airflow.
- There
is too little evaporator airflow.
- The
system is overcharged.
- The
system is undercharged.
- The
square root of the number 9 is:
- 1.5
- 2
- 3
- 6
- Air
flows from an 8-inch duct where the duct is reduced to 6 inches.
Which of the following is true?
- The
air velocity increases
- The
air velocity decreases
- The
CFM increases
- The
CFM decreases
- Which
of the following is true about compression ratio:
- It
is the absolute high side pressure divided into the absolute suction
pressure.
- It
is the absolute suction pressure divided into the absolute high side
pressure.
- It
is the high side pressure in psig divided into the suction pressure in
psig.
- It
is the suction pressure in psig divided into the high side pressure in
psig.
- The
speed of a three-phase motor is determined by:
- The
voltage to the motor
- The
current draw of the motor.
- The
frequency of the power supplied to the motor.
- The
number of poles in the motor.
- Which
one of the following fuse types should be used to protect the condensing
unit on a residential split system air conditioning system.
- Time-delay
- Instant
blow
- Fast
reacting
- Series
rated ground-fault
- Which
of the following organizations rates electrical components and equipment for
electrical safety?
- ARI
- UL
- RSES
- ASHRAE
- On a
heat pump the “balance point” is:
- The
point at which the heat loss of a structure matches the heat pump
capacity.
- The
point at which the heating load calculation matches the cooling load
calculation.
- The
lowest effective outside temperature at which the heat pump can operate.
- The
most effective temperature where the heat pump’s electric auxiliary heat
should be energized.
- On a
system using a reciprocating compressor, raising the evaporator pressure
and/or lowering the condensing pressure will:
- Decrease
the compressor’s volumetric efficiency.
- Increase
the compressor’s volumetric efficiency.
- Have
no effect of volumetric efficiency.
- Increase
the compressor’s power consumption.
- A
heat anticipator in a typical thermostat is wired:
- In
series with the “R” terminal
- In
parallel with the “R” terminal
- In
series with the “W” terminal
- In
parallel with the “W” terminal
- To
test a capacitor with an ohmmeter, the ohmmeter should be set at:
- The
R times 1 scale
- The
R times 10 scale
- The
R times 100 scale
- The
highest ohms scale available
- Which
of the following is considered a good evacuation?
- 2000
microns
- 1500
microns
- 1000
microns
- 500
microns or less.
- A
filter-drier has a temperature drop across it. Which of the following is true about the filter-drier?
- It
is partially plugged
- It
is totally plugged
- A
temperature drop across it is normal
- The
filter-drier has not yet broken in
- An
FRN-R fuse is:
- A
time delay fuse
- An
instant blow fuse
- Neither
A nor B is true
- Only
used on non-inductive circuits
- A
fuse must be selected according to:
- Type,
amperage and voltage
- Type
and amperage
- Type
and voltage
- Type,
amperage, voltage and wattage
- On a
typical three terminal single-phase fully hermetic compressor, between which
two terminals is the start winding located?
- The
two with the highest resistance
- The
two with the least resistance
- The
two with the middle resistance
- The
two with continuity to ground
- A
Ground Fault Circuit Interrupter monitors:
- The
current between the hot wire and ground
- The
current between the hot wire and the neutral wire
- The
current between the neutral wire and ground
- The
voltage across the line
- Typical
bypass humidifiers are connected:
- Between
the supply and the return ducts.
- Between
the supply and outside air intake
- Between
the outside air intake and return air duct
- Between
the exhaust air and return air ducts.
- The
typical bypass humidifier does not work well with which of the following
heating system types?
- Natural
gas
- Propane
gas
- Heat
pumps & electric heat
- Oil
fired furnaces
- During
the heating season a damper located in the bypass duct of a bypass
humidifier must be:
- Closed
- Open
- Adjusted
according to the temperature rise of the furnace
- Adjusted
according to the total cfm of the duct system.
- As
air is heated its relative humidity:
- Increases
- Decreases
- Remains
the same
- None
of these is correct
- A
sling Psychrometer measures:
- Dew
point temperature
- Specific
humidity
- Relative
humidity
- Dry
& wet bulb temperatures
- A
protractor is best used to:
- Measure
distance
- Layout
angles
- Determine
air velocity
- Select
a contractor
- Which
of the following is the most accurate method of balancing a duct system?
- Proportional
balancing
- Sequential
balancing
- Temperature
balancing
- Total
pressure balancing
- Which
of the following statements most correctly defines the difference between “accuracy” and “precision” in instruments?
- There
is no difference between the two terms.
- “Accuracy”
refers to how close the measurement is to the actual value being measured
while “precision” refers to how small a value can be measured.
- “Accuracy”
refers to how small a value can be measured while “precision” refers
to how close the reading is to the actual value.
- “Accuracy”
refers to the repeatability of the measurement while “precision”
refers to the percentage of error in the reading.
Prepared
by: Norm Christopherson
Norm
is a technical writer and seminar speaker.
He can be reached at nchristo@juno.com