The Concept
Of The Economizer
In a
nutshell
By
Norm Christopherson
The
function of the economizer is as its name implies, to “economize” or save on
cooling costs. Obviously, it costs
money to operate the compressor. If the compressor can be shut down and the
system still provide adequate cooling, energy savings can be realized.
Heat internal to the building
such as people, lights, computers, copy machines, motors and other machines
causes the temperature inside a structure to increase.
Heat soaked up by the building structure may also continue to heat the
building long after the temperature outside the building has dropped.
There are times when the temperature outside a building is lower than the
temperature inside.
Whenever the cooling system is
calling for cooling and the temperature outside is cool enough it is economical
to shut off the compressor and bring in cool outside air to satisfy the cooling
needs of the building. Such is the
function of an air economizer system.
There is one drawback to this
type of control system. Even though
the thermostat acknowledges that the outside air temperature is low enough to
cool the building, the outside air may be too humid to provide adequate comfort
for the building occupants. The
occupants will feel cool but clammy. The
solution is an economizer that adds a second control which works in harmony with
the outdoor thermostat and measures the outdoor air humidity.
Such a control is called an “enthalpy” control. The term
“enthalpy” means, total heat. The
enthalpy control measures both sensible and latent heat in the air and only
allows outside air to be used for cooling if the air is both cool and dry enough
to satisfy the space conditions.
If the indoor thermostat calls
for cooling and the outside air enthalpy (total heat) is low enough then the
economizer brings in this cooler and less humid air and uses it for cooling
instead of operating the compressor. Using the outside air for cooling is less
expensive than operating the compressor to provide cooling.
So an enthalpy control is a control which checks to see if both the temperature
(sensible heat) and the humidity (latent heat) are low enough to be used for
cooling. This combination provides for the greatest comfort at the least cost.
Not all economizers use
enthalpy controls. Some just check the outside air temperature and do not check
the outside air humidity. Those controls do not provide the same levels of
comfort as enthalpy controlled economizers.
Economizers can save a great
deal of energy. They can also waste energy if they are not operating properly or
are improperly adjusted. For
example, if the outside air dampers are not closing properly when the outside
air temperature is high, then hot air is unnecessarily entering the building and
causing the air conditioning compressor to operate longer and under higher loads
thus consuming a great deal more energy than necessary.
If the dampers are open too
far during the heating season the heating system must heat the extra outside air
entering the structure. Such extra
heating and cooling costs can be quite high.
The cost of a service call to repair such a problem is often less than
the cost of one or two months of energy wasted.
Many economizers are not
functioning at all or are out of service because they are not well understood by
some service technicians. Many
service technicians simply disable them. It
is essential that economizers are working properly and saving energy rather than
increasing costs.
Economizer
Maintenance
| Setting
& operation of the outdoor thermostat or enthalpy control. |
|
| Condition
of the outdoor thermostat or enthalpy control. |
|
| Proper
setting and operation of the economizer mixed air thermostat. |
|
| Proper
damper operation and lubrication. |
|
| Minimum
damper position adjustment. |
|
| Correct
operation of the system when a call for cooling comes from the thermostat. |
|
| Function
and condition of the economizer damper motor. |
|
| Condition
of the wiring and electrical terminations. |
Since the enthalpy control is
located in the outdoor air air-stream and is a relatively sensitive control, it
is not uncommon to have to replace it every few years depending upon the
location of the equipment and the weather extremes in the area. The cost of a
replacement control is usually recovered quickly through the energy saved.
Economizer service should be a part of the scheduled maintenance
performed at least on a yearly basis.
Just as our automobiles need
regular service so do residential and commercial heating & cooling systems.
Like automobiles, the frequency of service depends upon how it is
operated, how often & long it operates and the environment where it
operates. Like automobiles, well
maintained systems operate more efficiently, last longer and fail less often.
Norm is a technical writer, seminar speaker and test proctor for EPA, 410A and ESCO & NATE certifications.
He can be contacted at nchristo@juno.com