Draft
As
the fuel/air mixture (A) is delivered to the boiler, it is necessary that an
equal volume of flue gasses (B) enter boiler breach area.
As such, the draft rate is critical in maintaining this balance.
Draft diverters/hoods and barometric controls are designed to provide
varying degrees of draft control and allow dilution air to mix with the flue
gases to reduce the potential for condensation.
A single acting barometric
control is designed for fuel oil fired equipment while a double acting barometric
is only approved for gas-fired systems. The
double acting control door swings both directions to relieve downdrafts.
Both types of barometric dampers are capable of providing a constant
over fire draft, which is necessary to insure combustion air intake remains
consistent under varying chimney draft conditions.
Draft pressure is critical to the design of the
particular heating system and generally falls into one of four categories:
|
Atmospheric
systems are very common and depend entirely on the slightly negative stack
pressure (due to the heated flue gases being lighter than air and naturally
rising) to safely exhaust flue gases to the outside, while at the same time
pulling in sufficient combustion air. These
systems have draft diverters or hoods located immediately downstream from the
heat exchanger which allow room air to be pulled in and mixed with the
products of combustion before entering the vent system. |
|
|
Power
Burners have a mechanical blower, which delivers combustion air to the
flame, but also rely on a precisely controlled overfire draft to maintain
consistent combustion air intake. This
generally requires the installation of a barometric control. |
|
|
Balanced
Draft boilers, which are designed to operate under a positive pressure
in the combustion chamber, generally have a breach damper (either manually or
automatically controlled), which maintains the boiler combustion chamber and
flue gas passageways under a positive pressure to maximize efficiency.
Manufacturers’ positive pressure requirements vary widely.
However, a precisely controlled negative draft in the stack is still
required to remove the products of combustion at a controlled rate and to
allow for the exact amount combustion air to be introduced to the flame. |
|
|
Forced
Draft systems also have a mechanical
combustion air blower but are designed for a positive over fire pressure
created, in part, by resistance to flue gas flow in the stack, which also
operates under a positive pressure. |
To
check draft, a digital/mechanical draft gauge or inclined manometer is
necessary. As with combustion
testing, draft sample locations will vary depending on the type of equipment
tested.
While
it is of utmost importance to follow the equipment manufacturer’s
recommended draft readings, typical overfire draft measurements
are in the -.005 to -.02 Water Column Inch (WC”) range on both oil and gas power
burner systems.

Typically,
when a -.005 to -.02 WC” is measured over the fire, stack draft will be in
the -.02 to -.04 WC” range for gas fired power burners and -.04 to -.05 for
oil fired burners.
Stack
draft has been commonly used to set up barometric controls and evaluate draft
conditions, however, it does not necessarily guarantee correct over fire
pressure which is actually the main factor influencing combustion air intake.
The
combustion air intake on atmospheric equipment is so diffuse that overfire
draft readings generally cannot be obtained.
Consequently, draft must be measured immediately downstream from the
draft hood and should be in the -.02 to -.04 WC” range.
This will insure that there is stable, continuous negative pressure in
the combustion chamber to allow for the controlled introduction of air and
fuel.
Generally Acceptable Draft Measurements
|
Type
of Heating System |
Overfire
Draft |
Stack
Draft |
|
Gas,
Atmospheric Fan
Assist (80%) |
Not
Applicable |
-.02
to -.04 WC” |
|
Gas,
Power Burner |
-.02
WC” |
-.02
to -.04 WC” |
|
Oil,
Conventional |
-.01
to -.02 WC” |
-.02
to -.05 WC” |
|
Oil,
Flame Retention |
-.005
to -.02 WC” |
-.02
to -.04 WC” |
|
Positive
Over Fire Oil
and Gas |
+.4
to +.6 or
PMI |
-.02
to -.04 or
PMI |
Always
check with the manufacturer of a particular appliance to determine the
recommended overfire/stack draft requirements.
In
the past, many manufacturers recommend barometric controls be installed only
when high draft conditions exist. However,
field experience has shown that almost all vent systems are capable of producing
excess levels of draft during certain periods of the year and that even slight
variations in stack draft may influence combustion air intake.
In
situations where a barometric control has been installed and subsequent testing
determines high draft levels still exist, additional barometric controls can be
added.
Manufacturers
of barometric controls generally require that a manual reset spill
switch be installed on the barometric and wired to shut the burner down in the
event of an extended period of backdrafting
However,
keep in mind that a spill switch will most likely only trip when a chimney is
obstructed. If flue gas spillage is
caused by depressurization of the mechanical room , sufficient cold air may be
drawn down the stack to dilute flue gases sufficiently to not activate the spill
switch.

Where
multiple boilers are vented into the same chimney, attempts should be made to
balance the draft of each individual boiler with separate draft controls as
opposed to one draft control in the main breaching. For example, in the following diagram, draft controls should
be installed in location A or B. A
draft control in location C would not provide for sufficient draft control of each
individual boiler.
When common venting residential fan assist (80%) furnaces/boilers with
atmospheric hot water tanks (as is allowed by many manufacturers), great care
must be taken to insure the common vent functions under the wide variety of
operating conditions.
Forced
draft
boilers run a positive pressure from overfire, through to the stack termination.
The entire system must be welded or otherwise sealed tightly to prevent
flue gases from escaping. Also, the
height of the vent termination must be limited (generally 15 feet from the
breech) to prevent a negative draft. As
the vent system is operating under a positive pressure, barometric controls are not appropriate for
installation on this type system.

Taking
advantage of the potential for most efficient and reliable operation requires
more extensive testing be completed to properly set up this type equipment,
particularly when multiple units are commonly vented. Each needs to be tested under all conceivable operating
conditions.
Note: A draft
reading only measures
the difference in pressure between the inside and outside of the vent.
Combustion testing verifies
that these gases are being drawn from the combustion chamber/heat exchanger as
designed and at a sufficient rate to allow for additional introduction of the
proper fuel air mixture for combustion.
Combustion and draft testing also verifies that the heating equipment is operating as
designed and engineered by the manufacturer.
Also,
remember that the amount of positive or negative pressure in the firebox (over
the fire) of a gas-fired system will influence the fuel input as well.
| Return to Top |
| Next Page |